Garden City's water is supplied by Inc. Village of Garden City. The most recent published results show Copper at 0.066 mg/L, Lead at 9.3 µg/L. Every figure below is shown against its NY or EPA limit and cited to its source.

Reported contaminants

Garden City water, by the numbers

Data from Village of Garden City Water & Sewer Dept 2025 Water Quality Report · Verified 2026-11-11

ND means not detected. Units: µg/L is micrograms per liter (parts per billion); ng/L is nanograms per liter (parts per trillion); mg/L is milligrams per liter (parts per million). Status uses the words below, near, exceeds, or trace — not color alone.

Contaminants reported in Garden City, Nassau County drinking water, with detected level, regulatory limit, and status.
SubstanceDetected levelLimitStatusSource
PFAS
PFOS (about this substance)ND–4.3 ng/Lrange; no average published10NYS MCLBelow limitEPA UCMR 5 PFAS results, 2023–2025 (entry-point samples) (opens in a new tab)
PFNA (about this substance)ND–7.1 ng/Lrange; no average publishedNo regulatory limit—EPA UCMR 5 PFAS results, 2023–2025 (entry-point samples) (opens in a new tab)
Tested for and not detected (4): PFOA (about this substance), PFHxS (about this substance), PFBS (about this substance), HFPO-DA (about this substance)
Nitrate, metals & inorganics
Nitrate (about this substance)6.4 mg/LRange 0.2–6.410EPA MCLBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Chloride (about this substance)93.8 mg/LRange 21.0–93.8250NYS secondary standardBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Odor (about this substance)1.0 UnitsRange ND–1.03NYS secondary standardBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Combined Radium 226/228 (about this substance)1.49 pCi/LRange 0.34–1.495EPA MCLBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Chlorodifluoromethane (about this substance)1.4 µg/LRange ND–1.45.0EPA MCLBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Gross alpha (about this substance)3.44 pCi/LRange -0.16–3.4415EPA MCLBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Chloromethane (about this substance)1.0 µg/LRange ND–1.05.0EPA MCLBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Iron (about this substance)48.0 µg/LRange ND–48.0300NYS secondary standardBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Perchlorate (about this substance)2.5 µg/LRange ND–2.518EPA action levelBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Sulfate (about this substance)29.0 mg/LRange 11.8–29.0250NYS secondary standardBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Uranium (about this substance)3.31 µg/LRange 0.79–3.3130EPA MCLBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Gross beta (about this substance)4.64 pCi/LRange 2.31–4.6450EPA MCLBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Selenium (about this substance)2.2 µg/LRange ND–2.250EPA MCLBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Barium (about this substance)0.02 mg/LRange 0.0029–0.022.0EPA MCLBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Manganese (about this substance)0.09 mg/LRange ND–0.09300NYS secondary standardBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Sodium (about this substance)48.5 mg/LRange 12.7–48.5No regulatory limit—Inc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Nickel (about this substance)0.006 mg/LRange 0.001–0.006No regulatory limit—Inc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Calcium (about this substance)17.0 mg/LRange 7.85–17.0No regulatory limit—Inc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Magnesium (about this substance)7.1 mg/LRange 4.4–7.1No regulatory limit—Inc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Bromide (about this substance)0.13 mg/LRange 0.07–0.13No regulatory limit—Inc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Hexavalent Chromium (about this substance)1.0 µg/LRange ND–1.0No regulatory limit—Inc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Heptanal (about this substance)6.0 µg/LRange ND–6.0No regulatory limit—Inc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Alkalinity (about this substance)83.3 mg/LRange 3.7–83.3No regulatory limit—Inc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Total Dissolved Solids (about this substance)425.0 mg/LRange 71.0–425.0No regulatory limit—Inc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Lead & copper
Lead (about this substance)9.3 µg/L(90th percentile)Range ND–30.715EPA action levelBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Copper (about this substance)0.066 mg/L(90th percentile)Range ND–0.0871.3EPA action levelBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Disinfection byproducts
Bromoform (about this substance)0.53 µg/LRange ND–0.5380EPA MCLBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)
Total Trihalomethanes (about this substance)0.53 µg/LRange ND–0.5380EPA MCLBelow limitInc. Village of Garden City 2025 Annual Water Quality Report (opens in a new tab)

Water characteristics

Where the report prints only a range, status reflects the high end of that range; where it prints an average, status reflects the average.

Where the report prints both an average and a range, the status column here is judged on the average; where it prints a maximum or a 90th-percentile result, that figure is used. The report carries 2 notices: NOTICE OF VIOLATION (monitoring): 'During the periods from January 2024 to June 2024, July 2024 to December 2024, January 2025 to June 2025, and July 2025 to December 2025. We did not complete all monitoring for Lead and Copper, and therefore cannot be sure of the quality of your drinking water during that time.' Table - Copper, required sampling frequency 6 months: 47 of 60 samples taken Jul 2025 - Dec 2025; 48 of 60 Jan 2025 - Jun 2025; 39 of 60 Jul 2024 - Dec 2024; 59 of 60 Jan 2024 - Jun 2024. 'WE have made changes to our internal sample collecton procedures and will begin to collect additional copper samples as resident's request lead samples... For all of the sample results the Village did take, none of those sample results exceeded the action level for copper. During the time periods discussed previously, the Village has always collected the requisite number of lead samples.' 'This notice is specific to Copper samples only and not the overal Village water quality.' Sent by The Village of Garden City Water System, State Water System ID#:2902824. Lead action level exceedance (narrative, not labelled a violation): 90th percentile 9.3 ug/l with the AL of 15 ug/l exceeded at 6 of 70 sites, 'more than 10 percent of the homes tested' (p.4); p.5 lead public-education text advises residents with lead or unknown service lines to use bottled water or a certified filter until further notice; corrosion control (orthophosphate), lead sampling on request and public education program in place. 95% of Garden City's land lies inside a public water service area (Garden City (Village)), per the NYS Department of Health boundaries EPA publishes. A service area is where mains run; a home inside it can still be on a private well.

Your water district

Who supplies Garden City’s water

Check your water bill to confirm your district. More than one utility serves this town — the name on your bill is the one that matches your service.

EPA compliance

Federal violation record for Garden City’s suppliers

The annual report above lists what was found in the water. EPA’s compliance database records whether each supplier met its testing, treatment, and reporting obligations.

Compliance counts are EPA Safe Drinking Water Information System records pulled directly from EPA. Most violations are monitoring or reporting lapses, not unsafe water; health-based violations (a contaminant limit, disinfectant level, or treatment technique) are counted separately. A system listed for a ZIP code may serve only part of it.

What the numbers mean

Like most of Nassau, Garden City runs on treated public water. The day-to-day concerns here are the chlorine and chloramine used to keep the supply safe through the distribution system, plus the naturally high hardness of Long Island groundwater — the mineral content that leaves scale on fixtures and spots on glassware. Neither is an emergency, but both are exactly what point-of-entry carbon filtration and softening are designed to address.

What this means for filtration

Matching Garden City’s water to a system

For Garden City, the numbers point first to under-sink reverse osmosis and whole-house carbon filtration: dissolved contaminants close to their limits.

  • Recommended

    Under-Sink Reverse Osmosis

    Dissolved contaminants close to their limits

    Nitrate averaged 6.4 mg/L with samples up to 6.4 against a 10 mg/L limit — the closest number to its limit here. It passes straight through carbon; reverse osmosis is designed to reduce it at the tap. PFOA/PFOS reached 4.3 ng/L (ppt) in at least one sample — under New York's 10 ppt limit but at or above the 4.0 ppt federal MCL, with federal compliance due April 26, 2029. Whether an under-sink reverse osmosis model reduces PFOA or PFOS depends on that model's certification or performance data sheet. Sodium averaged 48.5 mg/L, above the 20 mg/L level New York flags for sodium-restricted diets. Perchlorate was detected up to 2.5 µg/L (limit 18). Hexavalent chromium averaged 1 µg/L; there is no federal limit for chromium-6 itself, and reverse osmosis reduces it. The supplier's 90th-percentile lead result was 0.0093 mg/L (9 ppb) against the 15 ppb action level. Lead enters water from a home's own service line and fixtures, so the system figure says little about any one house; a filter certified for lead (NSF/ANSI 53) or reverse osmosis at the kitchen tap reduces it at the point you drink.

    Explore Under-Sink Reverse Osmosis
  • Recommended

    Whole-House Carbon Filtration

    Chlorine residual 1.15 mg/L

    Free chlorine averaged 1.15 mg/L at the entry point (limit 4), the residual that gives tap water its pool taste and dries skin and hair.

    Explore Whole-House Carbon Filtration
  • Worth considering

    Whole-House + Softener Combo

    Hardness 69 mg/L, about 4.0 grains per gallon

    At 69 mg/L (4.0 gpg) the water is moderately hard. A softener is a comfort choice here, not a necessity.

    Explore Whole-House + Softener Combo

Questions

Garden City water FAQ

Free in-home test

See what’s really in your Garden City water.

Published reports cover the public supply — a free in-home test measures your taps (and your well, if you have one), then we walk you through the results.